 IEC60245-3 Glass Fiber Braid Silicone Rubber Wire

IEC60245-3 Glass Fiber Braid Silicone Rubber Wire

Conductor: Bare, tinned copper
Insulator: Silicone rubber
Glass fiber braiding
Silicone resin coating
Rated temp.: -60℃~180℃
Rated voltage: 300/500V
Test voltage: 2000V. 1min

Technical Parameters
Size Conductor Insulation thickness Braiding thickness Wire OD Resist.
Structure OD Nominal OD Nominal Tolerance Ω/KM
mm² No./mm mm mm mm mm mm Max.
0.25 14/0.15 0.65 0.60 1.85 0.20 2.25 ±0.15 80.9
8/0.20
0.35 20/0.15 0.75 0.60 1.95 0.20 2.35 ±0.15 55
11/0.20
0.5 28/0.15 0.95 0.60 2.15 0.20 2.55 ±0.15 40.1
16/0.20
0.75 24/0.20 1.15 0.60 2.35 0.20 2.75 ±0.15 26.7
1 32/0.20 1.34 0.60 2.55 0.20 2.95 ±0.20 20
1.5 30/0.25 1.60 0.70 3.00 0.20 3.40 ±0.20 13.7
2.5 49/0.25 2.00 0.80 3.60 0.25 4.10 ±0.25 8.21
4.0 56/0.30 2.70 0.80 4.30 0.25 4.80 ±0.30 5.09
6.0 84/0.30 3.30 0.80 4.90 0.25 5.40 ±0.30 3.39
10 84/0.40 4.60 1.00 6.60 0.25 7.10 ±0.30 1.95
16 126/0.40 5.80 1.00 7.80 0.25 8.30 ±0.40 1.24

Mechanical Properties
Tensile strength: ≥5N/mm²
Elongation at break of insulation: ≥150%
Min. bending radius: 6×OD

Characteristics
The braided synthetic yarn covering, which is applied directly over the insulation, gives the IEC60245-3 glass fiber braid silicone rubber wire, because of its short braiding pitch and high compactness, an excellent mechanical protection by maintaining good flexibility.
The varnishing of the braiding results in good antifriction properties, high abrasion resistance and excellent chemical resistance against transformer oil, light fuel oil and most types of cleaning agents.
In the event of fire, no corrosive and toxic gases will be given off.
Hence, damage caused by fire can be kept to minimum.