1. Home
  2. Products
  3. Mica Tape Wire
  4. AWM 5108 Fire Resistant Glass Fiber Braid Electric Wire
  AWM 5108 Fire Resistant Glass Fiber Braid Electric Wire

AWM 5108 Fire Resistant Glass Fiber Braid Electric Wire

Conductor: Nickel coated copper, pure nickel
Insulator: Fiber glass wrapping
Jacket: Glass fiber braiding
High temperature resin coating
Rated temp.: 250℃
Peak temp: 300℃
Rated voltage: 600V
Test VOLTAGE: 2000V. 1Min

Application
Mica tape wire is used for internal wire connection of high temperature environment of electric appliance like water heater, oven, furnace and aviation, military, etc.

Technical Parameters
Size Conductor Insulation Braid Wire OD Max
AWG Structure OD Thickness OD Nominal Toler. Resist.
NO. mm² No./mm mm mm mm mm mm mm Ω/KM
22 0.324 7/0.254 0.76 0.65 2.06 0.18 2.45 ±0.20 55
20 0.519 10/0.26 0.96 0.65 2.26 0.18 2.65 ±0.25 34.6
18 0.803 16/0.26 1.20 0.65 2.50 0.18 2.90 ±0.25 23.2
16 1.31 26/0.26 1.50 0.65 2.80 0.18 3.20 ±0.25 14.6
14 2.08 41/0.26 1.90 0.65 3.20 0.18 3.60 ±0.30 8.96
12 3.31 65/0.26 2.40 0.65 3.70 0.18 4.10 ±0.30 5.64
47/0.30
10 5.26 100/0.26 3.20 0.76 4.72 0.38 5.50 ±0.30 3.55
75/0.30
8 8.367 158/0.26 4.40 0.76 5.92 0.38 6.70 ±0.40 2.30
119/0.30
7 10.55 199/0.26 4.60 0.76 6.12 0.38 6.90 ±0.40 1.79
150/0.30
6 13.30 250/0.26 5.30 0.76 6.82 0.38 7.60 ±0.40 1.42
189/0.30
5 16.77 238/0.30 6.00 0.76 7.52 0.38 8.30 ±0.50 1.12
133/0.40
4 21.15 300/0.30 6.80 0.76 8.32 0.38 9.10 ±0.50 0.89
168/0.40
3 26.67 378/0.30 7.60 0.90 9.40 0.51 10.4 ±0.50 0.707
210/0.40
2 33.62 476/0.30 8.50 0.90 10.3 0.51 11.3 ±0.60 0.56
266/0.40
1 42.41 600/0.30 9.60 0.90 11.4 0.51 12.4 ±0.60 0.449
342/0.40
1/0 53.49 426/0.40 11.2 0.90 13.0 0.51 14.0 ±0.60 0.355
276/0.50
2/0 67.53 538/0.40 12.2 0.90 14.0 0.51 15.0 ±0.80 0.282
342/0.50
3/0 85.01 684/0.40 13.8 0.90 15.6 0.51 16.6 ±0.80 0.223
437/0.50
4/0 107.2 855/0.40 15.5 0.90 17.3 0.51 18.3 ±0.80 0.177
551/0.50

Standards
UL758, UL62, UL1581
Flame retardant acc. to IEC 60332-1
No flame propagation acc. to IEC 60332-3
Low smoke emission acc. to IEC 61034
Corrosiveness of combustion gases acc. to IEC 60754-2
Halogen free acc. to IEC 60754-1
Meet with RoHS, REACH rules.

Characteristics
The braided synthetic yarn covering, which is applied directly over the insulation, gives the cable, because of its short braiding pitch and high compactness, an excellent mechanical protection by maintaining good flexibility.
The varnishing of the braiding results in good antifriction properties, high abrasion resistance and excellent chemical resistance against transformer oil, light fuel oil and most types of cleaning agents.
In the event of fire, no corrosive and toxic gases will be given off.
Hence, damage caused by fire can be kept to minimum.